HumidiClean™Series HC- 6100/6300/6500/6700 HumidifiersInstallation, Operation andMaintenance InstructionsTable of ContentsPageWarning Labels 2-3Descr
Figure 10-1Standard HumidistatH200-XX-XX-XX10A18609 orA186100-10 VdcStat (Standard)A8581High LimitHumidistatA9023 Pressure SwitchModulating HighLimit
11SupplyControlSignal4-20ma Setup 10 vdc Setup1) S3-1 On, 3-2, 3, 4 Off (Default)2) S1-2 On, S1-1, 3 Off (Default)3) S2-1 On, S2-2, 3 Off if 4-20ma
High Limit HumidistatRemove the jumper tab from ground and in of high limit/pressure switch connections and wire the highlimit stat between these term
The menu can be accessed via the keypad below the LCD, on the front of electric cabinet. Use the UPor DOWN to change the menu in current level; press
14Enter Password 0000 (Default)Desired RHThis menu is displayed when RH sensor is selectedDesired RH: XX % Default: 50%Current RH: XX%Steam Generation
15Drain Frequency6 Default: 12 hours 12 (Default)244896No DrainReal TimeReal Time Set24 Hour ClockDrain Time15 (Default)10Load DefaultReset all to De
16Enter Password ARMHRun ModeRun (Default)TestContactor Count1234Control TypePWM (Default)On/OffPower Settings1000 W3000 W5000 W6650 W8000 WIonic Time
Principle of OperationThe HumidiClean humidifier converts ordinary tap water or purified water to steam for distribution toraise the relative humidity
Completing a Service Life CycleWhen 90% of the setting service time has accumulated, the "STATE" LED on the control panel willblink in yello
5) Restoring the Unit to Operationa) Turn power on at breaker.b) Unit should begin to fill. Maximum fill time is approximately 30-45 minutes before
The Armstrong HumidiClean humidifier converts ordinary tap water or purified water to steamfor distribution to raise the relative humidity level.To al
Figure 20-1 HC-6100/6300Figure 20-2 HC-6500/67004. Inspect tank drain screen and elements inside the tank. The elements should appear to be flaking of
9. Operate the unit configuration menu “Ionic Time Reset”, to reset the ionic bed life. All the accumulated ionic bed time has been reset to zero. The
Removing the Tank, HC-6100/6300 Only1. Operate menu to "MANUAL DRAIN" and allow unit to complete a deep drain. (Caution: Tank will still be
8. If drain valve and fill valve are both energized and water is below the 1/3 full level in the electrode canister (float canister for DI units), mak
4. If fuses are OK, check voltage to contactor coil.(a) If voltage is 24-28VAC at contactor coil, check coil resistance. It should be 8Ω with wires di
Humidifier runs continuously, %RH is well under set-point.1. Verify humidistat/RH sensor is wired correctly and dip switches (S2 & S3, See Fig. 1
Dispersion tube spits water or water is present in ductHint: It is very helpful to cut a small observation window in the duct and cover it with Plexig
2 WATER LEVEL DROPPED BELOW LOW LEVEL - - The low level switch has not closed after 5minutes of fill valve on time. This is only after initial start-
HC6100-Wye Wiring layout28
HC6100-Delta Wiring layout29
Warning: Do not operate the supplied humidifier in combustible or explosive surroundings.Warning: Do not operate the supplied humidifier if there is a
30HC6100-PAR Single Phase Wiring Layout
HC6300-Wye Wiring layout31
HC6300-Delta Wiring layout32
HC6500-Wye Wiring layout33
HC6500-Delta Wiring layout34
35HC6500-WYE (2 contactors) Wiring Layout
36HC6500-Delta (2 contactors) Wiring Layout
HC6700-Wye Wiring layout37
Item No. Water Compartment Part No.— PVC Tubing 5/8" A7618A— Clamp Hose Flat .63 Olive B2716-11— Hose Clamp, Minerature, Worm B2911-825Kit Fill V
39Without TC2PCS/UnitWith TC1PCS/UnitWithout TC 2PCS/UnitWith TC1PCS/Unit208 B5808-1 B5809-1 B5810-1 B5811-1240 B5808-2 B5809-2 B5810-2 B5811-2380 B58
• This disconnecting switch should have leakage current protecting function. The max leakage current should be less than 30mA• The disconnecting switc
40Item No.Electrical Compartment and Front PanelPart No.31 Label Front Panel With Keypad RDHC6000-01416 Emergency Stop Button RDEHU700-0651 Main PCB F
HC-6000 Repair Parts41Component Voltage Resistance Component Voltage ResistanceFill Valve 24Vac 18ΩFill Valve 24Vac 8.8ΩDrain Valve 24Vac 10ΩDrain Val
HC-6000 Repair Parts42Without TC 5PCS/UnitWith TC 1PCS/UnitWithout TC 5PCS/UnitWith TC 1PCS/UnitWithout TC 5PCS/UnitWith TC 1PCS/UnitWi
Procedure of HC6000 Version 7 Soft RefreshThis section is used for HC6000 software reprogramming only. Please follow the instructions carefully,or pc
Fig.2 Code Download Windowd. Click the "open folder" button on the right of textbox "Send File Name" to open the latest code, plea
e. Click the button "Send File" to send the latest code into board. You will be asked to unlock the involved lock regions (0 to 7), click th
g. When operation has finished, close the "SAM-BA" window first, and then click the icon "removethe USB hardware" to disconnect th
Table 46-1 Modbus Variable Lists 47data type attribute data address description10001 Fill valve status 0:off 1:on10002 Drain valve status 0:off 1:on
Table 47-1. BACnet Variable List48BACnet Data TypeData AddressDescription Attribute1 Fill valve status 0:off 1:on2 Drain valve status 0:off 1:on3 c
Table 48-1. LonWorks Variable List49Map Descriptor NameData Array NameData Array Offset Lon Function FunctionNode Name SNVT TypeSNVT optionoFILLST
5See Detail “A”Pitch Min. 1” Per12” Back to Unit2” Insulated Copper“P” Trap Drain Every20’ of Piping or atBottom of Vertical RunPitch Min. 1” Per 12”
50Knock-Out for Humidistat1” DrainElectrical SupplyKnock-Out forHumidistatAHGBJKEDMLRHCFPhysical Data, Capacities and Dimensional DrawingsFigure 49-1.
51Figure 135-1. Models HC-6500 and HC-6700 — Front, Side, Top ViewsQBGADEWater SupplyPort (UnderCabinet)HJKLMCFElectrical Supply(Under Cabinet)1” Drai
Armstrong International, Inc.Limited Warranty and RemedyArmstrong International, Inc. ("Armstrong") warrants to the original user of those p
InstallationHC-6100/6300 MountingThe HumidiClean models HC-6100/6300 are designed to be wall mounted. A wall mounting bracketand lag screws are provid
DrainageConnect HC-6000 drain to suitable waste drainage system. HC-6000 drain water may be as hot as 70°C (158°F). Use clear drain hose provided and
Duct Steam Distribution1. The dispersion tube should be proper length. Verify correct size from Table 8-1.2. Install dispersion tube(s) horizontally
Area Steam DistributionThe EHF-3 fan package (minimum of 2 required for HC-6500/6700) is designed to be hung on a wallto operate as a remote mounted,